temperature change from intake to exhaust is at least 12°F

Highlighted by rjhintz

If the equipment is free standing (or floor mounted), cooling air must be drawn in the front or bottom and discharged out the back or top of the unit

Highlighted by rjhintz

hardware manufacturer shall design the equipment with internal heat loads of more than 50 watts per rack unit for a temperature change from intake to exhaust (delta T) of not less than 15°F nor more than 20°F

Highlighted by rjhintz

most data centers use air conditioning equipment designed to provide approximately a 12°F (7°C) temperature difference between "cold" supply air and "hot" return air.

Highlighted by rjhintz

High heat density boxes would include any product or collection of products in a single footprint that exceeds 10 kW in power consumption.