The Uptime Institute - Cooling Compatibility Specification
Popularity Report
![]() |
|||
![]() |
|||
![]() |
|||
![]() |
|||
![]() |
|||
![]() |
URL Tag Cloud
Bookmark History
Saved by 1 people (0 private), first by anonymouse user on 2006-10-25
- Rjhintz on 2007-10-09 - Tags datacenters , hvac
Public Sticky notes
temperature
change from intake to exhaust is at least 12°F
Highlighted by rjhintz
If the equipment is free standing (or floor mounted), cooling air must be drawn in the front or bottom and
discharged out the back or top of the unit
Highlighted by rjhintz
hardware manufacturer shall design the equipment with internal heat loads of more than 50 watts per
rack unit for a temperature change from intake to exhaust (delta T) of not less than 15°F nor more than 20°F
Highlighted by rjhintz
most data centers use air conditioning equipment
designed to provide approximately a 12°F (7°C) temperature difference between "cold" supply air and "hot"
return air.
Highlighted by rjhintz
High heat density boxes would include any
product or collection of products in a single footprint that exceeds 10 kW in power consumption.